Kumwell KZ12.*.ds surge arrester Class II according to IEC 61643-11. These arresters are recommended for use in the Lightning Protection Zones Cencept at the boundaries of LPZ 1-2 (according to IEC 62305) for equip-otential bonding and ellmlnation of transient overvoltage that orlginate during atmospheric discharges or svvltching processes.
The main use of KZ12.*.ds arrester is in all kinds of industry, residential and administration buildings. They are to be placed into the secondary switchboards or into the control box.
| VARISTOR | ||||||
| Technical Data | KZ12.U0275.ds | KZ12.U0320.ds | KZ12.U0385.ds | KZ12.U0440.ds | ||
| Max. continuous operating voltage | UC | 275 V AC | 320 V AC | 385 V AC | 440 V AC | |
| Max. discharge current (8/20µs) | Imax | 50 kA | 50 kA | 40 kA | 40 kA | |
| Nominal discharge current (8/20µs) | In | 20 kA | 20 kA | 15 kA | 15 kA | |
| Voltage protection level at In | UP | < 2 kV | ||||
| Temporary overvoltage (TOV) | UT | 335 V/5 sec | 410 V/5 sec | 465 V/5 sec | 530 V/5 sec | |
| Response time | tA | < 25 ns | ||||
| Max. back-up fuse | 60 A gL/gG | |||||
| Short-circuit withstand capability | Ip | 60 kArms | ||||
| LPZ | 1-2 | |||||
| Protection type | IP20 | |||||
| Operating temperature range | -40°C to + 80°C | |||||
| Mounting on | Din rail 35 mm | |||||
| Failure indication | green (ok) / red (failure) | |||||