Kumwell KZ12.*.ds-3/0 is surge arrester class II according to IEC 61643-11. Complete device consists of a base part and pluggable module. These arresters are recommended for use in the Lightning Protection Zones Con-cept at the boundaries of LPZ 1-2 (according to IEC 62305) for equipotential bonding and elimination of transient overvoltage that originate during atmos-pheric discharges or switching processes.
The main use of KZ12.*.ds-3/0 arrester is in all kinds of industry, residential and administration buildings. They are to be placed into the secondary switchboards or into the control box.
Three-Phase for TN-C System | ||||||
Technical Data | KZ12.U0275.ds-3/0 | KZ12.U0320.ds-3/0 | KZ12.U0385.ds-3/0 | KZ12.U0440.ds-3/0 | ||
Max. continuous operating voltage | UN | 275 V AC | 320 V AC | 385 V AC | 440 V AC | |
Max. discharge current (8/20µs) | Imax | 50 kA | 50 kA | 40 kA | 40 kA | |
Nominal discharge current (8/20µs) | In | 20 kA | 20 kA | 15 kA | 15 kA | |
Voltage protection level at In | UP | < 1.3 kV | < 1.45 kV | < 1.65 kV | < 2.15 kV | |
Temporary overvoltage (TOV) | UT | 355 V / 5sec | 410 V / 5sec | 465 V / 5sec | 530 V / 5sec | |
Response time | tA | < 25 ns | ||||
Max. back-up fuse | 160 A gL/gG | |||||
Short-circuit withstand capability | Ip | 60 kArms | ||||
LPZ | 1-2 | |||||
Protection type | IP20 | |||||
Operating temperature range |
|
-40°C to + 80°C | ||||
Mounting on | Din rail 35 mm | |||||
Failure indication | green (ok) / red (failure) |